Inhaltsverzeichnis

Seite 1 - USER MANUAL

USER MANUAL On-Line UPS PowerWalker VFI 6000RT LCD PowerWalker VFI 6000P/RT LCD PowerWalker VFI 10000RT LCD Powe

Seite 2 - Contents

6  Ensure that no liquid or other foreign objects can enter the UPS.  The UPS can be operated by any individual without previous experi

Seite 3

7 5) Do not open or destroy batteries. Effluent electrolyte can cause injury to the skin and eyes. It may be toxic.  Please replace the fu

Seite 4

8 Power-frequency Magnetic field... :IEC/EN 61000-4-8 Level 3 Low Frequency Signals...:IEC/EN 61000-2-2 Warning: This is a product fo

Seite 5 - 1. Introduction

9 3. Installation This chapter explains:  Equipment inspection  Unpacking the cabinet  Checking the Accessory  UPS setup and installation 

Seite 6

10 Step 1: Open the outer carton and remove the accessories out of the carton (see Figure 3-1&3-2). Online R/T 6K UPS: Figure 3-

Seite 7

11 Step 2: With one person on each side, carefully lift the cabinet out of the outer carton using the handles on the cardboard and set it on a flat

Seite 8 - 2. Safety Warnings

12 Figure 3-4: Lifting the Cabinet out of 10K UPS carton Step 3: Discard or recycle the packaging i

Seite 9 - 2.2 Operation

13 10K model: Figure 3-6: Online R/T 10K Rear Panel 3.4 UPS Front Panel This section shows the f

Seite 10

14 3.5 Rack mount Setup CAUTION: The cabinet is heavy, so: 1) Remove the battery tray from the UPS before lifting. 2) Lifting the cabinets i

Seite 11 - 2.6 Standards

15 3. Pull the battery tray out using the plastic tabs and then remove the battery tray. Figure 3-11: Removing the Battery Tray 4. Install the

Seite 12

2 Uninterruptible Power Supply System Contents 1. Introduction ...

Seite 13 - 3. Installation

16 Figure 3-13. Install the sliding rails 7. For 10K---Install the battery pack and battery protection plate, then replace the front panel.

Seite 14 - Step 1:

17 To install EBMs: 6K Model: 1. Plug the EBM cable into the UPS battery connector Figure 3-15. Plug the EBM cable into the UPS battery connector 2.

Seite 15

18 10K Model: Figure 3-17. Plug the EBM cable into the UPS battery connector 3.6 Tower Setup Tower setup as below:

Seite 16 - 3.3 UPS Rear Panel

19 3.7 Installation of UPS with AC inputs CAUTION: Online 6K/10K series support that the UPS can have separate AC inputs. So before con

Seite 17 - 3.4 UPS Front Panel

20 2) Transformer in the Bypass AC input. 3) Both of them have transformer Frequency converter (without Bypass AC input)

Seite 18 - 3.5 Rack mount Setup

21 4. Power cables connection & Startup This section explains:  Access to terminal block  Common input sources connection  Separate input s

Seite 19

22 4.1 Access to terminal block Access to terminal block: remove the 2 screws of the terminal block cover Figure 4-1. PDU

Seite 20

23 Figure 4-2. Common input sources connection 4.3 Separate input sources connection CAUTION: This type of connection must be carried out by qua

Seite 21 - 6K Model:

24 4.4 Frequency converter connection Figure 4-4. Frequency converter connection 4.5 UPS Initial Startup To start up t

Seite 22 - 3.6 Tower Setup

25 7. Verify that the UPS is operating normally and any load is powered. 8. If optional EBMs are installed, see “Configuring the

Seite 23

8. Troubleshooting ... 52 8.1 Typical Alarms and Conditions ...

Seite 24

26 2) Users need to use a specialty 15-pin communication cable for this system, which should have 15 cores, corresponding stitches and shiel

Seite 25

27 Figure 4-5.a: Parallel systerm wiring diagram of 6K/10K

Seite 26 - 4.1 Access to terminal block

28 Figure 4-5.b: Parallel System Installation Diagram

Seite 27

29 6) Turn on the input breakers for the two parallel UPS. 7) Pressing button continuously for more than 1 second for one UPS of the syst

Seite 28 - 4.5 UPS Initial Startup

30 4) Set the main maintenance switch or static switch from “UPS” to “BPS”, then switch off the main output breaker and the input breaker and mai

Seite 29

31 5. Operation 5.1 Display Panel The UPS has a four-button graphical LCD with dual color backlight. Standard back-light is used to light up the disp

Seite 30

32 Enter main menu When displaying default UPS status summary screen, press this button for >1s to enter the main menu tree Exit main menu Pres

Seite 31

33 After powering on, the LCD will display Welcome logo for several seconds and then enter to the default page which shows the UPS status s

Seite 32

34 Table 5-3 Status Summary Screens Status Summary Screen Description Fig 5-3 Normal mode: The UPS is operating in Normal mode from utility power. Fi

Seite 33

35 software (Winpower, etc.). 2) It is attention that the transfer time of UPS output from HE mode to battery mode is about 10ms. But it is st

Seite 35 - 5. Operation

36 Fig 5-11 Overload: When the UPS is overload, the alarm will beep twice every second. Some unnecessary loads should be get rid of one by one

Seite 36

37 4) A few seconds later, the UPS turns into Line mode. If the utility power is abnormal, the UPS will transfer to Battery mode without ou

Seite 37 - 5.2 Operating mode

38 5.4 LCD operation Except the default UPS status summary screen, the user could get more useful information about UPS current status, detailed vari

Seite 38

39 Figure. 5-14 Main menu tree

Seite 39

40 5.4.2 The UPS status menu By pressing on the menu of “UPS status”, the display would enter the next UPS status menu tree. The content of UPS st

Seite 40

41 Figure. 5-15 Event menu tree 5.4.4 The measurement menu By pressing on the menu of “Measurement”, the display would en

Seite 41

42 Figure. 5-16 Measurement menu tree 5.4.5 The control menu By pressing on the menu of “Control”, the display would enter the

Seite 42

43 to reset error status, then UPS would stop alarm and recover to Bypass mode. And the reason of fault should be checked and deleted before UPS is t

Seite 43 - Figure. 5-14 Main menu tree

44 5.4.6 The identification menu By press on the menu of “Identification”, the display would enter the next identification menu tree. The

Seite 44

45 potential failures or protecting function loss, even directly damage the load, battery or UPS. Most of settings could only be done while UPS is in

Seite 45 - Figure. 5-15 Event menu tree

1 1. Introduction This Online R/T Series is an uninterruptible power supply incorporating double-conversion technology. It provides perf

Seite 46

46 Example: set rated output voltage value Figure. 5-20 Set rated output voltage value

Seite 47

47 6. UPS Maintenance This chapter explains how to:  Care for the UPS and batteries  Transport the UPS  Store the UPS and batteries  Test t

Seite 48

48 4. Disconnect the internal battery connectors 5. Replace the UPS front cover 6.3 Storing the UPS and Batteries If you store the UPS for a l

Seite 49

49 During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25% of the original expected runtime.

Seite 50

50 7. Specifications This chapter provides the following specifications:  Model list  General Specification  Electrical Performance  Environmenta

Seite 51 - 6. UPS Maintenance

51 Current 26.4A@230Vac 44.0A@230Vac Power Factor ≥ 0,99 @100% Nominal Load ≥ 0,98 @50% Nominal Load ≥ 0,95 @25% Nominal Load THDI < 5 %@Full loa

Seite 52 - 6.4 Testing Batteries

52 8. Troubleshooting The online series UPS is designed for durable, automatic operation and issues alarms to alert you whenever poten

Seite 53

53 Site Wiring Fault Alarm Code: 04 Site Fault detection is supported on all models anytime there is a Grounding Neutral connection. Alarm triggers

Seite 54 - 7. Specifications

54 Output Overload Alarm Code:41 Output is overload. Remove some of the equipment from the UPS. The UPS continues to operate, but may switch to Bypas

Seite 55 - 7.3 Operating Environment

55 BUS Over Voltage Alarm Code:21 Indicates that the UPS get BUS over voltage fault because of BUS. The UPS transfers to Bypass mode if supporting th

Seite 56 - 8. Troubleshooting

2 Figure 1-2: Online R/T 10K UPS Online R/T UPS as Tower installation. Figure 1-3: Online R/T 6

Seite 57

56 Parallel cable loss Alarm Code: E2 In parallel system,parallel cable disconnect Disconnect parallel cable one turn to fault mode Parallel system b

Seite 58

57 9. Communication This chapter contains:  Communication ports (RS-232 and USB)  Network Management Card (Optional)  UPS Management Software 

Seite 59

58 7 Not used -- 8 On Battery signal Out 9 Vdc Power(+12V) This pin is connected via a jumper to pin 2 of SNMP connector Out Figure.9-2

Seite 60

59 9.2 Network Management Card (Optional) Network Management Card allow the UPS to communicate with different types of devices in variety of ne

Seite 61 - 9. Communication

60 Installation procedure: Connected by USB to a PC or notebook, the Software enables communication between the UPS and the computer. The UPS softwar

Seite 62

3 Providing outstanding performance and reliability, the UPS’s unique benefits include:  Online UPS design with pure sine wave output.  True onl

Seite 63

4 2. Safety Warnings IMPORTANT SAFETY INSTRUCTIONS FOR EACH STEP SAVE THESE INSTRRUCTIONS. 2.1 Installation  Condensation may occur if

Seite 64 - 9.4 REPO Function

5 the neutral conductor should be provided in the building wiring installation.  This is permanently connected equipment , it must be installed by