AS-400 Card Quick Guide
V.2.0
Product Outlook
1
3
Installation
2
Product Introduction
The AS400 communication card provides contact closures for remote monitoring
your UPS. To meet different application requirement, the AS400 card is capable of
selection the status of the dry-contact signal (active close or active open) by setting
jumper. This suitable applications are listed below:
IBM Server, Personal PC & Workstations equipments
Auto-controlled industrial equipment & communication applications
Step 1: Remove cover of Intelligent
Slot on the rear panel of the UPS.
Cover of
Intelligent Slot
Step 2: Insert AS400 card into Intelligent
Slot.
Step 3: The cover of AS400 should attach
close to the rear panel. Using screwdriver,
secure the AS400 to the UPS chassis with
2 screws.
Step 4: Use the 9-pin communication
cable to connect UPS and equipment to
implement the remote monitoring and
control.
9-pin communication cable
Internal circuit of DB-9 port
Specifications
4
Pin Assignment
Pin Assignment Function I/O
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Pin 9
UPS Failure
UPS Audible Alarm
GND (Common for Pin 4)
Remote Shutdown
Common for relays
Bypass Active
Low Battery
UPS On
Utility Failure
O/P
O/P
Power Ground
I/P
Power Supply
O/P
O/P
O/P
O/P
AC status ReasonAO status
Pin 1 & Pin 5 connected Pin 1 & Pin 5 disconnected UPS internal failure
Pin 2 Pin 2 & Pin 5 connected & Pin 5 disconnected
UPS failure, utility failure,
low battery, bypass active
Pin 6 Pin 6 Bypass active
Pin 7 & Pin 5 connected Pin 7 & Pin 5 disconnected Battery voltage is low
Pin 8 & Pin 5 connected Pin 8 & Pin 5 disconnected UPS is in inverter mode
Pin 9 & Pin 5 connected Pin 9 & Pin 5 disconnected Utility failure
& Pin 5 connected & Pin 5 disconnected
Function Description
P.S. The shutdown pin (pin4 & pin3) only accepts 3-10s high level signal to perform
the UPS shutdown.
Top View
Side View
1N4148W
UPS Failure
UPS Audible
Alarm
Remote Shutdown
Common
Bypass
Low Battery
UPS On
Utility Failure
2K/0.1W
Electric Parameter of DB-9 port
Parameter Symbol MAX. Min. UNIT
Diode
Relay
DC Current
Reverse Voltage
Forward Current
Peak Forward Current
DC Voltage
DC Current
6
6
50
1
24
1.0
mA
V
mA
A
V
A
Resistor*
V
R
I
F
I
F(peak)
V
DC
I
DC
I
R
1
-
-
-
-
-
Note: Its required to retain the DC current lower than 6mA. Otherwise, its
necessary to add one resistor within DC current limitation in the serial loop of
Remote Shutdown. (e.g. 2K resistor with at least 0.1W rating power). Refer to
diagrams in Application.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - AS-400 Card Quick Guide

AS-400 Card Quick Guide V.2.0Product Outlook13Installation2Product IntroductionThe AS400 communication card provides contact closures for remote monit

Seite 2 - Jumper Set-up

Internal Logic Connection5Jumper Set-up6Below shows the circuit of basic application to implementmonitoring and control.Application:User Interface for

Kommentare zu diesen Handbüchern

Keine Kommentare